4 Faults and alarms
4.2 List of faults and alarms
F01359
Topology: DRIVE-CLiQ performance not sufficient
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The DRIVE-CLiQ performance is not sufficient at one line in order to identify an inserted component.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- Distribute components across several DRIVE-CLiQ lines.
Note:
For this topology, do not withdraw and insert components in operation.
F01360
Topology: Actual topology not permissible
Message value:
Fault cause: %1, preliminary component number: %2
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The detected actual topology is not permissible.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex:
cccc = preliminary component number, bb = no significance, aa = fault cause
aa = 01 hex = 1 dec:
Too many components were detected at the Control Unit. A maximum of 199 components is permissible.
aa = 02 hex = 2 dec:
The component type of a component is not known.
aa = 03 hex = 3 dec:
It is illegal to combine ALM and BLM.
aa = 04 hex = 4 dec:
It is illegal to combine ALM and SLM.
aa = 05 hex = 5 dec:
It is illegal to combine BLM and SLM.
aa = 06 hex = 6 dec:
A CX32 was not directly connected to a permitted Control Unit.
aa = 07 hex = 7 dec:
An NX10 or NX15 was not directly connected to a permitted Control Unit.
aa = 08 hex = 8 dec:
A component was connected to a Control Unit that is not permitted for this purpose.
aa = 09 hex = 9 dec:
A component was connected to a Control Unit with out-of-date firmware.
aa = 0A hex = 10 dec:
Too many components of a particular type detected.
aa = 0B hex = 11 dec:
Too many components of a particular type detected on a single line.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
For fault cause = 1:
Change the configuration. Connect less than 199 components to the Control Unit.
For fault cause = 2:
Remove the component with unknown component type.
1408
Propagation:
LOCAL
Propagation:
LOCAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150