Siemens G130 List Manual page 1387

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Reaction upon F:
Vector: NONE (OFF1, OFF2, OFF3, STOP2)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
F01068
CU: Data memory memory overflow
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The utilization for a data memory area is too large.
Fault value (r0949, interpret binary):
Bit 0 = 1: High-speed data memory 1 overloaded
Bit 1 = 1: High-speed data memory 2 overloaded
Bit 2 = 1: High-speed data memory 3 overloaded
Bit 3 = 1: High-speed data memory 4 overloaded
Remedy:
- deactivate the function module.
- deactivate drive object.
- remove the drive object from the target topology.
A01069
Parameter backup and device incompatible
Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter backup on the memory card and the drive unit do not match.
The module boots with the factory settings.
Example:
Devices A and B. are not compatible and a memory card with the parameter backup for device A is inserted in device
B.
Remedy:
- insert a memory card with compatible parameter backup and carry out a POWER ON.
- insert a memory card without parameter backup and carry out a POWER ON.
- save the parameters (p0977 = 1).
F01070
Project/firmware is being downloaded to the memory card
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
An upgrade (project/firmware download) was initiated on the memory card.
While this fault is present, the corresponding update takes place with plausibility and consistency checks. After this,
depending on the command option, a new boot (reset) for the Control Unit is initiated.
Caution:
During the upgrade and while this fault is present, it is not permissible to switch off the Control Unit.
If the operation is interrupted, this can destroy the file system on the memory card. The memory card will then no
longer work properly and must be repaired.
Remedy:
Not necessary.
The fault is automatically withdrawn after the upgrade has been completed.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Propagation:
GLOBAL
Propagation:
GLOBAL
Propagation:
GLOBAL
4 Faults and alarms
4.2 List of faults and alarms
1387

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents