4 Faults and alarms
4.2 List of faults and alarms
See also: p3109 (UTC synchronization tolerance)
Remedy:
Select the synchronization intervals shorter so that the deviation between the time of day master and drive system
lies within the tolerance.
Note:
The deviation when synchronizing is shown in r3107.
See also: r3107 (UTC synchronization time out of tolerance)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A01100
CU: Memory card withdrawn
Message value:
-
Message class:
General drive fault (19)
Drive object:
B_INF, VECTOR_G
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory card (non-volatile memory) was withdrawn during operation.
Notice:
It is not permissible for the memory card to be withdrawn or inserted under voltage.
Remedy:
- switch off the drive system.
- re-insert the memory card that was withdrawn - this card must match the drive system.
- switch on the drive system again.
F01105 (A)
CU: Insufficient memory
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
OFF1
Acknowledge:
POWER ON
Cause:
Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets,
Technology Extensions, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, Technology
Extensions, blocks, etc).
- use an additional Control Unit.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01106
CU: Insufficient memory
Message value:
%1
Message class:
Hardware/software error (1)
Drive object:
B_INF, TM150, VECTOR_G
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
There is not sufficient free memory space available.
Remedy:
Not necessary.