4 Faults and alarms
4.2 List of faults and alarms
F01072
Memory card restored from the backup copy
Message value:
-
Message class:
General drive fault (19)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The Control Unit was switched-off while writing to the memory card. This is why the visible partition became
defective.
After switching on, the data from the non-visible partition (backup copy) were written to the visible partition.
Remedy:
Check that the firmware and parameterization is up-to-date.
A01073 (N)
POWER ON required for backup copy on memory card
Message value:
-
Message class:
General drive fault (19)
Drive object:
All objects
Component:
Control Unit (CU)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter assignment on the visible partition of the memory card has changed.
In order that the backup copy on the memory card is updated on the non-visible partition, it is necessary to carry out
a POWER ON or hardware reset (p0972) of the Control Unit.
Note:
It is possible that a new POWER ON is requested via this alarm (e.g. after saving with p0971 = 1).
Remedy:
- carry out a POWER ON (switch-off/switch-on) for the Control Unit.
- carry out a hardware reset (RESET button, p0972).
Reaction upon N:
NONE
Acknowl. upon N:
NONE
F01082
Parameter error when powering up from data backup
Message value:
Parameter: %1, Index: %2, fault cause: %3
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Component:
None
Reaction:
Vector: OFF2 (NONE, OFF1, OFF3)
Infeed: OFF2 (NONE, OFF1)
Acknowledge:
IMMEDIATELY
Cause:
Parameterizing errors have been detected (e.g. incorrect parameter value). It is possible that the parameter limits are
dependent on other parameters.
The detailed cause of the fault can be determined using the fault value.
Fault value (r0949, interpret hexadecimal):
ccbbaaaa hex
aaaa = Parameter
bb = Index
cc = fault cause
0: Parameter number illegal.
1: Parameter value cannot be changed.
2: Lower or upper value limit exceeded.
3: Sub-index incorrect.
4: No array, no sub-index.
5: Data type incorrect.
6: Setting not permitted (only resetting).
7: Descriptive element cannot be changed.
9: Descriptive data not available.
11: No master control.
1388
Propagation:
LOCAL
Propagation:
LOCAL
Propagation:
LOCAL
List Manual (LH2), 07/2016, A5E03263479A
SINAMICS G130/G150