Configure Transformer - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Measurement > Configure Transformer
ID
Parameter
1854
Mains current
input
1852
Mains current
measuring
4.2.1

Configure Transformer

General notes
98
CL
Setting range
Description
[Default]
1Ph 2W
Measurement is performed Line-Neutral (WYE connected system) if param‐
eter
nected system) if parameter
Measurement, display and protection are adjusted according to the rules for
phase-phase systems.
Monitoring refers to the following voltages:
n
1Ph 3W
Measurement is performed Line-Neutral (WYE connected system) and Line-
Line (Delta connected system).
The protection depends on the setting of parameter
urement, display, and protection are adjusted according to the rules for
single-phase systems.
Monitoring refers to the following voltages:
n
n
n
Notes
If this parameter is configured to 1Ph 3W, the generator and mains rated vol‐
tages (parameters
Line (Delta) and the busbar 1 rated voltage (parameter
be entered as Line-Neutral (WYE).
2
[Mains cur‐
This parameter configures whether ground or mains current is measured on
rent] / Ground
terminals 1/2 or the input is disabled.
current / Off
2
[Phase L1] /
Phase L{1/2/3} Measurement is performed for the selected phase only. The
Phase L2 /
measurement and display refer to the selected phase.
Phase L3
The configured phase CT must be connected to perform current measure‐
ment.
Notes
For information on measuring principles refer to
Current" on page 64 .
This parameter is only effective if mains voltage measuring (param‐
eter
The setpoints for specific parameters will differ depending upon the
hardware version, indicated on the data plate.
[1] easYgen-2xxx-1 = Current transformer with ../1 A rated cur‐
n
rent
[5] easYgen-2xxx-5 = Current transformer with ../5 A rated cur‐
n
rent
easYgen-2200/2500 | Genset Control
1858 Ä p. 95
is configured to "Phase - neutral" and Line-Line (Delta con‐
1858 Ä p. 95
VL1N, VL12
VL13 (parameter
1771 Ä p. 135
VL1N, VL3N (parameter
1771 Ä p. 135
VL1N, VL3N (parameter
1771 Ä p. 135
1766 Ä p. 95
and
1853 Ä p.
97) is configured to "3Ph 4W" or "3Ph 3W".
is configured to "Phase - phase".
1771 Ä p.
135. Meas‐
configured to "Phase-phase")
configured to "Phase-neutral")
configured to "All")
1768 Ä p.
95) must be entered as Line-
1781 Ä p.
95) must
Ä Chapter 3.2.6.2 "Mains
37535B