Load share bus communication - "normal" refreshed data
Mux
Byte
Bit
4-7
6
0-3
4,5
6
7
7
Load share bus communication - "normal" refreshed data
Mux
Byte
Bit
N1
0
1
2
3
4
5
0
1
2
3
37535B
Data Protocols > CANopen > Protocol 6000 (Load Share...
Function
Reactive load control state
Engine state
Operating mode
Generator request
Not used
Not used
Function
2
Generator reactive load, L-Byte, L-Word
Generator reactive load, H-Byte, L-Word
Generator reactive load, L-Byte, H-Word
Generator reactive load, H-Byte, H-Word
Generator voltage and frequency ok
Busbar voltage and frequency ok
Mains voltage and frequency ok
Fourth system voltage and frequency ok
easYgen-2200/2500 | Genset Control
Appendix
Remark
2: Static
3: Isochronous
4: Reactive load control
5: Import/export reactive load
10:Reactive load share
0, 1, 6, 7, 8, 9, 11, ... : internal
1: Locked out
2: Off
3: Preglow
4: Crank
5: Run
6: Cool down
7: Spin down
8: Start pause
9: Idle
0, 10, 11, ... : internal
0: Not available
1: STOP
2: MANUAL
3: AUTOMATIC
Generator is in AUTOMATIC mode
and able to produce rated active
power
Remark
Mux identifier
Long [var]
523