Configuration
Configure Application > Configure Controller > Load Control
ID
Parameter
5502
Slip frequency
setpoint offset
5505
Phase
matching gain
5506
Phase
matching df-
start
5508
Freq. control
initial state
(Frequency con‐
trol initial state)
4.5.12.2

Load Control

ID
Parameter
5525
Load Control
5513
Proportional
gain
276
CL
Setting range
Description
[Default]
Example
n
n
n
n
n
n
2
0.00 to 0.50 Hz
This value is the offset for the synchronization to the busbar/utility.
[0.10 Hz]
With this offset, the unit synchronizes with a positive slip.
Example
If this parameter is configured to 0.10 Hz and the busbar/mains frequency is
50.00 Hz, the synchronization setpoint is 50.10 Hz.
2
1 to 99
The phase matching gain multiplies the setting of the proportional gain
(parameter
[5]
2
0.02 to 0.25 Hz
Phase matching will only be enabled if the frequency difference between the
systems to be synchronized is below the configured value.
[0.05 Hz]
2
0.0 to 100.0 %
The value entered for this parameter is the start reference point for the analog
output to the speed controller.
[50.0 %]
Notes
If the output to the speed control has been disabled, the output will act as a
control position reference point.
CL
Setting range
Description
[Default]
2
[PID analog]
The generator load is controlled using an analog PID controller.
3pos controller
The generator load is controlled using a three-step controller.
Off
Load control is not carried out.
2
0.01 to 100.00
The proportional coefficient specifies the gain. By increasing the gain, the
response is increased to permit larger corrections to the variable to be con‐
[1.00]
trolled.
The farther out of tolerance the process is the larger the response action is to
return the process to the tolerance band.
easYgen-2200/2500 | Genset Control
Rated power: 500 kW
Rated frequency setpoint: 50.0 Hz
Droop 5.0 %
Active power: 0 kW = 0 % of rated power
Frequency is adjusted to: (50.0 Hz – [5.0 % * 0.0 * 50 Hz]) = 50.0 Hz.
Active power: +250 kW = +50 % of rated power
Frequency is adjusted to: (50.0Hz – [5 % * 0.50 * 50 Hz]) = 50.0 Hz –
1.25 Hz = 48.75 Hz.
Active power: +500 kW = +100 % of rated power
Frequency is adjusted to: (50.0Hz – [5 % * 1.00 * 50 Hz]) = 50.0 Hz –
2.5 Hz = 47.50 Hz.
5510 Ä p.
271) for phase matching control.