Installation
Setup Connections > Voltage Measuring > Busbar Voltage
3.2.5.3

Busbar Voltage

General notes
Schematic and terminals
56
The easYgen-2000 Series can only measure either
the busbar voltage (described in this chapter) or the
mains voltage (Ä Chapter 3.2.5.2 "Mains Voltage"
on page 50). The device is not able to measure both
voltages at the same time.
If parameter
rated volt.") is configured with a value between 50 and
130 V, the 120 V input terminals must be used for
proper measurement.
If parameter
rated volt.") is configured with a value between 131
and 480 V, the 480 V input terminals must be used for
proper measurement.
Fig. 37: Voltage measuring - busbar - wiring
Terminal
Description
A
22
Busbar (Mains) voltage -
phase L1
B
23
C
24
Busbar (Mains) voltage -
phase L2
D
25
E
26
Busbar (Mains) voltage -
phase L3
F
27
G
28
Busbar (Mains) voltage -
phase N
H
29
Table 17: Voltage measuring - busbar - terminal assignment
easYgen-2200/2500 | Genset Control
1803 Ä p. 100
("Mains PT secondary
1803 Ä p. 100
("Mains PT secondary
120 Vac
480 Vac
120 Vac
480 Vac
120 Vac
480 Vac
120 Vac
480 Vac
A
max
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
37535B