Miscellaneous; Alarm Acknowledgement - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Parameter
Description
Monitoring
Monitored data source
Monitoring at
Limit
Hysteresis
Delay
Alarm class
Self acknowledgment
Delayed by engine speed
Table 44: Flexible limits - configuration examples
4.4.6

Miscellaneous

4.4.6.1

Alarm Acknowledgement

ID
Parameter
1756
Time until horn
reset
37535B
Configure Monitoring > Miscellaneous > Alarm Acknowledgement
Refer to
on page 179 for configuration examples. The analog inputs must
be configured accordingly.
Example for low oil pressure monitoring Example for high coolant temperature
Oil pressure
On
06.01 Analog input 1
Underrun
200 (2.00 bar)
10
0.50 s
F
No
Yes
CL
Setting range
Description
[Default]
0
0 to 1,000 s
After each alarm of alarm class B through F occurs, the alarm LED flashes
and the horn (command variable 03.05) is enabled. After the delay time "time
until horn reset" has expired, the horn (command variable 03.05) is disabled.
The alarm LED flashes until the alarm has been acknowledged either via the
push button, the LogicsManager, or the interface.
Notes
If this parameter is configured to 0, the horn will remain active until it will be
acknowledged.
easYgen-2200/2500 | Genset Control
Ä "Flexible limits - configuration examples" Table
monitoring
Coolant temp.
On
06.02 Analog input 2
Overrun
80 (80 °C)
2
3 s
B
No
No
Configuration
179