Engine operation in AUTOMATIC
(basic function)
6.2.3

Application Mode A03 (GCB)

37535B
Basic Applications > Application Mode A03 (GCB)
Engine starts, if
The LogicsManager "Start req. in AUTO" is fulfilled (TRUE)
n
AND
A shut down alarm is not present AND
n
The engine is ready for operation
n
With successful start the GCB closure is released.
Engine stops, if
The reply GCB is open AND the LogicsManager "Start req. in
n
AUTO" is not fulfilled (FALSE) OR
A shut down alarm occurs
n
Being parallel to mains or to other generator, the generator power
will be reduced before.
Refer to Ä Chapter 4.5.11 "Automatic Run"
on page 246 for details.
This application mode (
only the GCB is operated by the easYgen.
If it is used for isolated or mains parallel operations, mains decou‐
pling should be performed by the GCB or an external provision.
The easYgen will function as an engine control with generator and
engine protection. The control unit can open and close the GCB.
Emergency mode (AMF operation) is not supported in this applica‐
tion mode.