LogicsManager Reference > Logical Command Variables > Group 04: Applications Con...
No.
ID
Name
04.01
239
Auto mode
04.02
240
Stop mode
04.03
241
Manual mode
04.04
242
Lamp test
04.05
243
Acknowledge
04.06
244
GCB closed
04.07
245
MCB closed
04.08
246
Reserved
04.09
247
Emergency
mode
04.10
248
Cool down
04.11
249
Mains settling
04.12
250
Start w/o load
04.13
251
Remote request
04.14
252
Remote
acknowledge
04.15
253
Idle run active
04.16
254
Reserved
04.17
255
Reserved
04.18
256
Synchron. GCB
active
04.19
257
Opening GCB
active
04.20
258
Closing GCB
active
04.21
259
Syn. MCB is
active
04.22
260
Opening MCB
active
04.23
261
Closing MCB
active
04.24
262
Reserved
04.25
263
Reserved
04.26
264
Reserved
37535B
These operating statuses may be used as command variable in a
logical output to set parameters for customized operations.
Function
AUTOMATIC operating mode active
STOP operating mode active
MANUAL operating mode active
A lamp test is being performed
"Acknowledge" push button has
been pressed or an external
acknowledgment via LogicsManager
GCB is closed
and
MCB is closed
only
Emergency power operation active
Engine cool-down cycle active
Mains settling time active
Start without closing GCB is active
Request over remote control to acti‐
vate a function
Request over remote control to
acknowledge
Idle mode is active
Synchronization GCB is active
Opening GCB is active
Closing GCB is active
Synchronization MCB is active
Opening MCB is active
Closing MCB is active
easYgen-2200/2500 | Genset Control
Note
TRUE in AUTOMATIC operating mode
TRUE in STOP operating mode
TRUE in MANUAL operating mode
TRUE if the lamp test is active
This condition is TRUE for approx. 40 ms and must be
extended utilizing a delay time
TRUE if DI 8 (Reply GCB) is de-energized
TRUE if DI 7 (Reply MCB) is de-energized
TRUE with the expiration of the emergency power
delay; FALSE with the expiration of the mains setting
time and the reply from the MCB is closed
TRUE as long as the cool down time is running
Becomes TRUE with a mains failure and FALSE after
the mains settling timer has expired
TRUE if Start w/o load is enabled
TRUE if the start bit is set via serial connection
(Modbus) or CAN bus (CANopen), (control word 503)
TRUE if this bit is set via interface (control word 503)
TRUE if the idle mode is active. This may be used to
issue an "Idle" command to a speed controller.
TRUE if the GCB shall be synchronized until the GCB is
closed
TRUE if a GCB open command is issued until DI 8
(Reply GCB) is energized
TRUE if a GCB close command is issued; same func‐
tion as relay 6 in
or
TRUE if the MCB shall be synchronized until the MCB is
closed
TRUE if an MCB open command is issued until DI 7
(Reply GCB) is energized
TRUE if an MCB close command is issued; same func‐
tion as relay 8 in
Appendix
565