Woodward easYgen-2000 Series User Manual page 307

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
12900
Discrete f/P +
12901
Discrete f/P -
12902
Discrete V/PF + 2
12903
Discrete V/PF -
37535B
Configure Application > Configure Controller > Discrete Raise/Low/Function
Frequency and voltage may be adjusted within the configured
operating limits (
Frequency" on page 107 ). Active power may be adjusted between
0 and the configured load control setpoint maximum (param‐
eter
5523 Ä p.
0.71 leading and 0.71 lagging.
CL
Setting range
Description
[Default]
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, the frequency /
LogicsManager
load setpoint will be raised.
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, the frequency /
LogicsManager
load setpoint will be lowered.
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
Determined by
Once the conditions of the LogicsManager have been fulfilled, the voltage /
LogicsManager
reactive power setpoint will be raised.
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, the voltage /
LogicsManager
reactive power setpoint will be lowered.
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
easYgen-2200/2500 | Genset Control
Ä Chapter 4.4.1.1 " Generator Operating Voltage /
280). The power factor may be adjusted between
The parameters listed below can be only configured
via ToolKit.
Configuration
307