Installation
Setup Connections > Voltage Measuring > Generator Voltage
3.2.5.1.5
Parameter Setting '1Ph 2W' (1-phase, 2-wire)
'1Ph 2W' Phase-Neutral Measuring
Generator windings
Table 9: Generator windings - 1Ph 2W (phase neutral)
Measuring inputs
Terminal assignment
1Ph 2W
Wiring terminals
Rated voltage (range)
120 V (50 to 130 V
Measuring range (max.)
0 to 150 Vac
Terminal
A
48
For different voltage systems, different wiring terminals
have to be used.
Incorrect measurements are possible, if both voltage
systems use the same N terminal.
The 1-phase, 2-wire measurement may be performed
phase-neutral or phase-phase.
Please note to configure and wire the easYgen
consistently.
Fig. 29: Measuring inputs - 1Ph 2W (phase neutral)
)
eff.
C
E
G
easYgen-2200/2500 | Genset Control
480 V (131 to 480 V
)
eff.
0 to 600 Vac
B
D
F
H
37535B