IKD 1 configuration
ID
Parameter
-
CAN Node-ID
-
CAN ID receive
data
-
CAN ID send
data
-
Physical state
only
Table 74: IKD 1 configuration
Fig. 163: IKD 1 configuration
(example LeoPC1)
Fig. 164: IKD 1 configuration
(example LeoPC1)
Baud rate configuration
37535B
Special Applications > Connecting An IKD 1 On CAN...
Refer to the IKD 1 Manual 37135 for the configuration of the unit
and the parameters concerned. Please note that the DPC cable (P/
N 5417-557) together with the LeoPC1 software (delivered with the
DPC cable) is required to configure the IKD 1.
Configure IKD 1 as shown below to communicate with an
easYgen.
Value
Comment
0
The CAN Node-ID is configured to 0
385 (dec)
The CAN ID for receive data is configured to 385 (dec)
513 (dec)
The CAN ID for send data is configured to 513 (dec)
Yes
Only the physical state of the IKD 1 inputs is evaluated
ð (Fig. 163) and (Fig. 164) display the example IKD 1 con‐
figuration.
The baud rate must be configured identical in the easYgen and the
IKD 1. The following example shows the configuration of both units
to 250 kBd.
easYgen-2200/2500 | Genset Control
Application
385