Remote Start/Stop And Acknowledgement - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Special Applications > Performing Remote Start/St... > Remote Start/Stop And Ackn...
Example for test without load
ID
Parameter
1663
Active day
1662
Active hour
Table 71: Timer configuration
Fig. 154: LogicsManager function
Fig. 155: LogicsManager function
"Start without load"
6.4.4.3

Remote Start/Stop And Acknowledgement

Start request in AUTOMATIC oper‐
ating mode
37535B
The unit will open the MCB and close the GCB. When the mains
return, it will transfer the load back to the mains according to the
configured breaker transition mode after the mains settling timer
has expired. The engine will keep running until the conditions for
"Start w/o load" are FALSE again.
The engine shall start once a month and run for one hour without
overtaking the load. The test day shall be every fifteenth of a
month (with flag 2). A relay output can be configured to indicate if
this test is running, e.g. for a signal lamp.
1.
Configure the parameters listed below to set up the timer.
Value
Comment
15
The active day is enabled every fifteenth of the month
10
The active hour is enabled between 10:00 and 11:00 am every day
2.
Configure the LogicsManager function "Flag 2" (parameter
12240 Ä p.
ð Flag 2 becomes TRUE as soon as the configured active
day and active time is reached.
"Flag 2"
3.
The LogicsManager function "Start without load" (parameter
12540 Ä p.
ð Start without load mode is enabled as soon as Flag 2
becomes TRUE.
The easYgen may be started, stopped, or acknowledged with
Modbus or CAN protocol via the interface.
Two logical command variables are available for this in the Logi‐
csManager:
04.13 Remote request
n
04.14 Remote acknowledge
n
1.
Either on the front panel or using ToolKit navigate to menu
"Configure automatic run" .
2.
Open the LogicsManager for entry "Start req in AUTO".
easYgen-2200/2500 | Genset Control
324) as shown in (Fig. 154).
247) can be configured as shown in (Fig. 155).
Application
379

Advertisement

Table of Contents
loading

Table of Contents