Magnetic Pickup Unit - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

4.5.9.3

Magnetic Pickup Unit

37535B
Configure Application > Engine > Magnetic Pickup Unit
To configure the MPU input, the number of teeth on the flywheel
detected by the magnetic pick up (MPU) or the number of pickup
pulses per revolution of the engine must be configured.
Ä "MPU input - typical configurations" Table on page 241 shows
the speed measuring range for various flywheel teeth numbers
(parameter
1602 Ä p.
eter
1601 Ä p.
95) for a minimum signal voltage of 2 V.
Fly wheel teeth
Rated speed
[rpm]
5
1500
5
1800
5
3000
5
3600
10
750
10
1500
10
1800
10
3000
10
3600
25
750
25
1500
25
1800
25
3000
25
3600
50
750
50
1500
50
1800
50
3000
50
3600
100
750
100
1500
100
1800
100
3000
100
3600
150
750
150
1500
150
1800
150
3000
150
3600
easYgen-2200/2500 | Genset Control
242) and rated speeds (param‐
Minimum voltage
[V]
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Configuration
Speed measuring
range [rpm]
700 to 10000
700 to 10000
700 to 10000
700 to 10000
350 to 10000
350 to 10000
350 to 10000
350 to 10000
350 to 10000
135 to 10000
135 to 10000
135 to 10000
135 to 10000
135 to 10000
65 to 10000
65 to 10000
65 to 10000
65 to 10000
65 to 10000
35 to 5000
35 to 5000
35 to 5000
50 to 5000
50 to 5000
25 to 5000
35 to 5000
35 to 5000
35 to 5000
35 to 5000
241