Configuration
Configure Application > Analog Outputs 3/4
4.5.8

Analog Outputs 3/4

Data source
Source value at minimal output
Source value at maximal output
Filter time constant
Selected hardware type
(For details refer to
Ä "Analog outputs - signal type
selection" Table on page 228 )
User defined min. output value
User defined max. output value
General notes
226
Type
Setting in parameter
5201/5215
20 to 0mA (10 to 0V)
User defined
Table 52: Analog outputs - signal type selection
The analog outputs 3 and 4 may only be used for 0/4 to 20 mA.
The outputs are freely scalable. Any analog source of the analog
manager can be passed to these outputs.
The following table shows the default values for the analog out‐
n
puts 3 and 4.
ID
Analog output 3
default values
5228
00.01 Engine speed
5232
0
5234
10000
5231
3
5229
Off
5236
---
5237
---
Parameters
have a meaning unless parameter
set to "user defined".
When an external resistor (burden) of 500 Ohm (0.25
W / 0.1 %) is applied to the analog outputs 3 and 4, the
hardware type for voltage can also be used.
easYgen-2200/2500 | Genset Control
Jumper
Range
neces‐
sary
10 to 0V
ID
Analog output 4
default values
5242
00.01 Engine speed
5246
0
5248
10000
5245
3
5243
Off
5250
---
5251
---
5236 Ä p. 228
and
5237 Ä p. 228
5229 Ä p. 227
Lower
Upper
level
level
10 Vdc
0 Vdc
don't
is
37535B