Appendix
LogicsManager Reference > Logical Command Variables> Group 00: Flags Condition 1
No.
ID
00.12
11
00.13
12
00.14
13
00.15
14
00.16
15
00.17
16
00.18
17
00.19
18
00.20
19
00.21
20
00.22
21
00.23
22
00.24
23
00.25
24
558
Name
LM: Undelay close GCB
Reserved
LM: Constant idle run
LM: External acknowledge
LM: Operation mode AUTO
LM: Operation mode MAN
LM: Operation mode STOP
LM: Start w/o load
LM: Automatic idle mode
LM: Discrete f/P +
LM: Discrete f/P -
LM: Discrete V/PF +
LM: Discrete V/PF -
LM: Freq. Droop active
easYgen-2200/2500 | Genset Control
Function
Immediately closing of the GCB
without waiting for the engine
delayed monitoring timer to
expire
Constant idle speed mode ena‐
bled (blocks alarm for under‐
voltage, underfrequency, and
underspeed constantly)
The alarm acknowledgement is
performed from an external
source
Activation of the AUTOMATIC
operating mode
Activation of the MANUAL op.
mode
Activation of the STOP oper‐
ating mode
Starting the engine without
closing the GCB
Automatic idle speed mode
(blocks alarm for undervoltage,
underfrequency, and under‐
speed automatically for a set
time)
Raise frequency / real power
setpoint
Lower frequency / real power
setpoint
Raise voltage / power factor
setpoint
Lower voltage / power factor
setpoint
Frequency droop active
Note
Internal calculation
Refer to parameter
12210 Ä p.
204.
Internal calculation
Refer to parameter
12550 Ä p.
243.
Internal calculation
Refer to parameter
12490 Ä p.
180.
Internal calculation
Refer to parameter
12510 Ä p.
247.
Internal calculation
Refer to parameter
12520 Ä p.
247.
Internal calculation
Refer to parameter
12530 Ä p.
248.
Internal calculation
Refer to parameter
12540 Ä p.
247.
Internal calculation
Refer to parameter
12570 Ä p.
243.
Internal calculation
Refer to parameter
12900 Ä p.
307.
Internal calculation
Refer to parameter
12901 Ä p.
307.
Internal calculation
Refer to parameter
12902 Ä p.
307.
Internal calculation
Refer to parameter
12903 Ä p.
307.
Internal calculation
Refer to parameter
12904 Ä p.
275.
37535B