Woodward easYgen-2000 Series User Manual page 97

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
1850
Generator cur‐
rent measuring
1853
Mains voltage
measuring
37535B
CL
Setting range
Description
[Default]
1Ph 3W
Measurement is performed Line-Neutral (WYE connected system) and Line-
Line (Delta connected system). The protection depends on the setting of
parameter
Measurement, display, and protection are adjusted according to the rules for
single-phase systems.
Monitoring refers to the following voltages:
n
n
Notes
If this parameter is configured to 1Ph 3W, the generator and mains rated vol‐
tages (parameters
Line (Delta) and the busbar 1 rated voltage (parameter
be entered as Line-Neutral (WYE).
For information on measuring principles refer to
Voltage" on page 43 .
2
[L1 L2 L3 ]
All three phases are monitored. Measurement, display and protection are
adjusted according to the rules for 3-phase measurement. Monitoring refers
to the following currents: IL1, IL2, IL3
Phase L{1/2/3}
Only one phase is monitored. Measurement, display and protection are
adjusted according to the rules for single-phase measurement.
Monitoring refers to the selected phase.
Notes
This parameter is only effective if generator voltage measuring (param‐
eter
For information on measuring principles refer to
Current" on page 62 .
2
[3Ph 4W]
Measurement is performed Line-Neutral (WYE connected system) and Line-
Line (Delta connected system). The protection depends on the setting of
parameter
Phase voltages and the neutral must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
WYE connected systems.
Monitoring refers to the following voltages:
n
n
n
3Ph 3W
Measurement is performed Line-Line (Delta connected system). Phase vol‐
tages must be connected for proper calculation.
Measurement, display and protection are adjusted according to the rules for
Delta connected systems.
Monitoring refers to the following voltages:
n
easYgen-2200/2500 | Genset Control
1770 Ä p.
107.
VL13 (parameter
1770 Ä p. 107
VL1N, VL3N (parameter
1770 Ä p. 107
1766 Ä p. 95
and
1851 Ä p.
96) is configured to "3Ph 4W" or "3Ph 3W".
1771 Ä p.
135.
VL12, VL23 and VL31 (parameter
phase")
VL1N, VL2N and VL3N (parameter
neutral")
VL12, VL23, VL31, VL1N, VL2N and VL3N (parameter
configured to "All")
VL12, VL23, VL31
Configuration
Configure Measurement
configured to "Phase-phase")
configured to "Phase-neutral")
1768 Ä p.
95) must be entered as Line-
1781 Ä p.
95) must
Ä Chapter 3.2.5.1 "Generator
Ä Chapter 3.2.6.1 "Generator
1771 Ä p. 135
configured to "Phase-
1771 Ä p. 135
configured to "Phase-
1771 Ä p. 135
97