Discrete inputs
DI
Alarm class
1
F
2
CONTROL
3
B
4
B
5
CONTROL
6
CONTROL
7
8
9
B
10
B
9.5

Event And Alarm Reference

9.5.1

Alarm Classes

Alarm class
Visible in the dis‐
play
A
Yes
Warning Alarm
This alarm does not interrupt the unit operation. A message output without a centralized alarm occurs:
n
Alarm text.
B
Yes
Warning Alarm
This alarm does not interrupt the unit operation. An output of the centralized alarm occurs and the command
variable 3.05 (horn) is issued.
n
Alarm text + flashing LED "Alarm" + Relay centralized alarm (horn).
C
Yes
Shutdown Alarm
With this alarm the GCB is opened and the engine is stopped. Coasting occurs.
n
Alarm text + flashing LED "Alarm" + Relay centralized alarm (horn) + GCB open + Coasting + Engine stop.
D
Yes
37535B
freely configurable
freely configurable
freely configurable
freely configurable
freely configurable
freely configurable
fixed
fixed
freely configurable
freely configurable
The control functions are structured in the following
alarm classes:
LED "Alarm"
Relay "Command:
open GCB"
& horn
No
No
Yes
No
Yes
Soft unloading
Yes
Immediately
easYgen-2200/2500 | Genset Control
Event And Alarm Reference > Alarm Classes
Pre-assigned to
EMERGENCY STOP
LogicsManager Start in
AUTO
Low oil pressure
Coolant temperature
LogicsManager External
acknowledgement
LogicsManager Enable
MCB
Reply MCB
Reply GCB
unassigned
unassigned
Shut-down engine
No
No
Cool down time
Cool down time
Appendix
Engine blocked
until ack.
sequence has
been performed
No
No
Yes
Yes