Advertisement

Fig. 97: Derating of power (example)
ID
Parameter
15143
Start derating
at
15144
Stop derating
at
15145
Max. power
deviation
15147
Source free
derating
15146
Free derating
37535B
Configure Application > Configure Controller > Derating Of Power
CL
Setting range
Description
[Default]
2
-032000 to
This parameter defines the starting point when the derating becomes active.
032000
The value applies to the analog source (parameter
[1000]
2
-032000 to
This parameter defines (in combination with parameter
032000
ramp of the derating function.
[0]
2
1.0 to 100.0 %
This parameter defines the maximal power deviation of the derating function.
That means it determines also the minimal power while derating is active.
[100.0 %]
The configured percentage for the max. power deviation refers to the gener‐
ator rated active power (parameter
2
Analog Manager
This parameter defines the analog source which controls the derating func‐
tion.
[Analog input
1]
2
Determined by
This LogicsManager equation releases the free derating function.
LogicsManager
(24.60)
[False]
easYgen-2200/2500 | Genset Control
If the derating signals are digital (e.g. different relay
outputs), the digital signals can be transformed to an
analog signals with a simple set of resistors.
1752 Ä p.
Configuration
15147 Ä p.
283).
15143 Ä p.
283) the
95).
283