ID
Parameter
3308
Preglow time
[tPH]
(Diesel engine)
3347
Preglow mode
(Diesel engine)
3346
Preglow crite‐
rion
(Diesel engine)
3309
Preglow tem‐
perature
threshold
3310
Ignition delay
[tID]
(Gas Engine)
3311
Gas valve
delay [tGD]
(Gas Engine)
3312
Minimum
speed for igni‐
tion
(Gas Engine)
37535B
CL
Setting range
Description
[Default]
Notes
All functions which are described here, may be assigned by the LogicsMan‐
ager to any relay that is available via the LogicsManager and not assigned to
another function.
2
0 to 999 s
Prior to each start, the diesel engine is preheated for this time (if a "0" has
been configured here the engine will be started without preglow).
[5 s]
Notes
The display indicates "Preglow".
2
This parameter dictates if and under what conditions a diesel engine is pre‐
heated.
Off
The diesel engine is never preheated before a start attempt.
[Always]
Before a start attempt the "Preheating" relay is always energized for the pre‐
glow time (parameter
Analog
A preglow sequence is initiated if the monitored analog input temperature
(coolant temperature) is below the configured threshold (param‐
eter
preglow time (parameter
2
Determined by
The preglow criterion may be selected from the available data sources.
AnalogManager
Usually, a temperature measuring is selected here, which is measured via a
[06.01]
sensor.
Notes
Refer to
sources.
2
-10 to 250 °C
This is the temperature threshold, which must be exceeded to prevent a pre‐
heating process, if parameter
[0 °C]
2
1 to 999 s
With gas engines often a purging operation is desired before starting.
[5 s]
With the engaging of the starter the ignition delay is started. The display indi‐
cates "Turning".
If the "Minimum speed for ignition" is reached after the expiration of this time,
the ignition is energized.
2
0 to 999 s
By energizing the ignition relay the gas valve delay is started ("Ignition" is dis‐
played).
[5 s]
After the time set here has expired, and as long as the speed is higher than
the minimum speed for ignition, the gas valve is enabled for the time config‐
ured in parameter
Once the ignition speed has been reached, the gas valve remains opened. If
the speed falls below ignition speed, the gas valve will be closed and the
"Ignition" relay is de-energized 5 seconds later.
2
10 to 1,800 rpm
After expiration of the ignition delay the number of revolutions set here must
be reached, so the "Ignition" relay will be energized.
[100 rpm]
easYgen-2200/2500 | Genset Control
Configure Application > Engine > Engine Type
3308 Ä p.
231). After that a start attempt is initiated.
3309 Ä p.
231). The preglow sequence is enabled for the configured
3308 Ä p.
Ä Chapter 9.3.1 "Data Sources" on page 533 for a list of all data
3347 Ä p. 231
3306 Ä p. 238
"Starter time" ("Start" is displayed).
Configuration
231). After that a start attempt is initiated.
has been set to "Analog".