Fig. 169: RPDO configuration for 2nd
IKD 1 (example HMI)
Fig. 170: RPDO configuration for 2nd
IKD 1 (example ToolKit)
6.4.6
Configuring A PWM Duty Cycle For A CAT ADEM Controller
37535B
Special Applications > Configuring A PWM Duty Cyc...
2.
Set up RPDO2 for the easYgen on the front panel as shown
in (Fig. 169).
ð Set up RPDO2 for the easYgen in ToolKit as shown in
(Fig. 170).
If a PWM signal shall be used with a CAT ADEM speed controller,
the duty cycle must be limited between 10 % and 85 %.
For this, the following settings must be made to the respective
analog output
The following parameter IDs and figures refer to
analog output 1.
Note, that another analog output may also be used.
easYgen-2200/2500 | Genset Control
Application
387