3.2.5.3.1
Parameter Setting '3Ph 4W' (3-phase, 4-wire)
Busbar windings
Table 18: Busbar windings - 3Ph 4W
Measuring inputs
Terminal assignment
3Ph 4W
Wiring terminals
Rated voltage (range)
120 V (50 to 130 V
Measuring range (max.)
0 to 150 Vac
Terminal
A
22
Phase
L1
37535B
Setup Connections > Voltage Measuring > Busbar Voltage
Fig. 38: Measuring inputs - 3Ph 4W
)
eff.
C
E
G
24
26
28
L2
L3
N
For different voltage systems, different wiring terminals
have to be used.
Incorrect measurements are possible if both voltage
systems use the same N terminal.
easYgen-2200/2500 | Genset Control
480 V (131 to 480 V
)
eff.
0 to 600 Vac
B
D
F
23
25
27
L1
L2
L3
Installation
H
29
N
57