Woodward easYgen-2000 Series User Manual page 368

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Application
Multiple Genset Applications
Fig. 142: Multiple genset application (schematic)
Configuration example
368
The following example describes the configuration of a typical iso‐
lated parallel operation and load-dependent start/stop.
The load dependent start/stop function (LDSS) shall be enabled
with a remote start request and during emergency operation. LDSS
shall depend on the reserve power on the busbar. In case of a
dead busbar (caused by a mains failure) all capable generators
shall be started and operated with their minimum running time.
No generator priority is considered. Generator selection shall be
performed depending on the operating hours.
The following assumptions are valid for the example:
3 generators, each with 80 kW rated power, are available.
n
The recommended minimum load for the generators is 40 kW.
n
The minimum running time is 180 s.
n
easYgen-2200/2500 | Genset Control
37535B