Configuration
Configure Application > Configure Breakers
ID
Parameter
4062
Self acknowl‐
edge
4060
Monitoring
4063
Number of
gens commu‐
nicating
4.5

Configure Application

4.5.1

Configure Breakers

General notes
190
CL
Setting range
Description
[Default]
2
Yes
The control automatically clears the alarm if the fault condition is no longer
detected.
[No]
The control does not automatically reset the alarm when the fault condition is
no longer detected. The alarm must be acknowledged and reset by manually
pressing the appropriate buttons or by activating the LogicsManager output
"External acknowledgement" (via a discrete input or via an interface).
2
On
Multi-unit missing members monitoring is carried out.
[Off]
Monitoring is disabled.
2
2 to 32
The number of units participating in load sharing is configured here.
[2]
easYgen-2200/2500 | Genset Control
The assignment of the defined relays to defined func‐
tions occurs by selection of the application mode (i.e.
function "Command: Close GCB" on relay [R 6], this
relay can no longer be operated via the LogicsMan‐
ager).
The same way some relays are designated to specific
functions, others may be assigned to different func‐
tions. These are listed as "programmed" relays. If a
relay is "programmable" the function may be assigned
to other relays via the LogicsManager by configuration.
For additional information refer to Ä Chapter 4.5.5
"Discrete Outputs (LogicsManager)" on page 220.
If the easYgen is intended to be operated in parallel
with the mains, the mains voltage measuring inputs
must be connected. If an external mains decoupling is
performed, jumpers between busbar and mains
voltage measuring inputs may be installed.
Changing the application mode will not change other
configured values in the parameters. The application
mode parameter is the only one.
37535B