Application
Special Applications > Start/Stop Logic Mode "Off"
Fig. 194: Start/Stop sequence - LogicsManager "Firing speed"
402
Fig. 194 shows the following:
The frequency controller is triggered, if the engine speed (gen‐
n
erator frequency) reaches the "Start frequency control level"
(parameter
5516 Ä p.
quency control delay" (parameter
quency controller is switched off, if the engine speed (gener‐
ator frequency) falls below the "Firing speed" (parameter
12500 Ä p.
239) level.
The voltage controller is triggered, if the generator reaches the
n
"Start value" (parameter
"Start delay" (parameter
troller is switched off, if the engine speed (generator frequency)
falls below the "Firing speed" (parameter
level.
The delayed monitoring function is triggered when LogicsMan‐
n
ager "Firing speed" (parameter
TRUE and after the "Engine monitoring delay time" (parameter
3315 Ä p.
239). The delayed monitoring function is switched
off when LogicsManager "Firing speed" (parameter
12500 Ä p.
239) becomes FALSE.