Mains Overfrequency (Level 1 & 2) Ansi# 81O - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Mains > Mains Overfrequency (Level...
ID
Parameter
3110
Mains decou‐
pling
3113
Mains decou‐
pling feedback
delay
3111
Alarm class
3112
Self acknowl‐
edge
4.4.2.3
Mains Overfrequency (Level 1 & 2) ANSI# 81O
General notes
138
CL
Setting range
Description
[Default]
2
[GCB]
Mains decoupling is carried out according to the following parameters. If one
of the subordinate monitoring functions is triggered, the GCB will be opened.
If the unit is operated in parallel with the mains and the MCB opens, the GCB
will be closed again.
GCB->MCB
Mains decoupling is carried out according to the following parameters. If one
of the subordinate monitoring functions is triggered, the GCB will be opened.
If the reply "GCB open" is not present within the delay configured in param‐
eter
MCB->GCB
Mains decoupling is carried out according to the following parameters. If one
of the subordinate monitoring functions is triggered, the MCB will be opened.
If the reply "MCB open" is not present within the delay configured in param‐
eter
MCB
Mains decoupling is carried out according to the following parameters. If one
of the subordinate monitoring functions is triggered, the MCB will be opened.
Off
Mains decoupling monitoring is disabled.
2
0.10 to 5.00 s
If the open signal from the respective circuit breaker cannot be detected
within the time configured here, the mains decoupling function performs the
[0.40 s]
action as configured in parameter
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[B]
Notes
For additional information refer to
on page 587 .
2
Yes
The control automatically clears the alarm if the fault condition is no longer
detected.
[No]
The control does not automatically reset the alarm when the fault condition is
no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
There are two overfrequency alarm levels available in the control.
Both alarms are definite time alarms and are illustrated in the figure
below. The figure diagrams a frequency trend and the associated
pickup times and length of the alarms. Monitoring of the frequency
is accomplished in two steps.
Refer to
for the triggering characteristic of this monitoring function.
easYgen-2200/2500 | Genset Control
3113 Ä p.
138, the MCB will be opened as well.
3113 Ä p.
138, the GCB will be opened as well.
3110 Ä p.
Ä Chapter 9.5.1 "Alarm Classes"
If this protective function is triggered, the display indi‐
cates "Mains overfreq. 1" or "Mains overfreq. 2" and
the logical command variable "07.06" or "07.07" will be
enabled.
Ä Chapter 9.1.1 "Triggering Characteristics" on page 481
138.