Installation
Setup Connections > Voltage Measuring > Busbar Voltage
3.2.5.3.2
Parameter Setting '3Ph 3W' (3-phase, 3-wire)
Busbar windings
Measuring inputs
Terminal assignment
3Ph 3W
Wiring terminals
Rated voltage (range)
120 V (50 to 130 V
Measuring range (max.)
0 to 150 Vac
Terminal
A
22
Phase
L1
58
Table 19: Busbar windings - 3Ph 3W
Fig. 39: Measuring inputs - 3Ph 3W
)
eff.
C
E
G
24
26
28
L2
L3
---
For different voltage systems, different wiring terminals
have to be used.
easYgen-2200/2500 | Genset Control
480 V (131 to 480 V
)
eff.
0 to 600 Vac
B
D
F
23
25
27
L1
L2
L3
H
29
---
37535B