Configuration
Configure Application > Configure Breakers > Breakers MCB
ID
Parameter
5711
Pos. freq. dif‐
ferential MCB
(Positive fre‐
quency differen‐
tial MCB)
5712
Neg. freq. dif‐
ferential MCB
(Negative fre‐
quency differen‐
tial MCB)
5713
Max positive
phase angle
MCB
(Maximum per‐
missible positive
phase angle
MCB)
5714
Max negative
phase angle
MCB
(Maximum per‐
missible nega‐
tive phase angle
MCB)
5717
Phase
matching MCB
dwell time
3431
Dead bus clo‐
sure MCB
12923
Enable MCB
206
CL
Setting range
Description
[Default]
Notes
This value refers to the generator rated voltage (parameter
mains rated voltage (parameter
If the difference between mains and busbar voltage does not exceed the
value configured here and the mains voltage is within the operating voltage
window (parameters
MCB close" may be issued.
2
0.02 to 0.49 Hz
The prerequisite for a connect command being issued for the MCB is that the
differential frequency is below the configured differential frequency.
[0.18 Hz]
This value specifies the upper frequency (positive value corresponds to posi‐
tive slip → busbar frequency is higher than the mains frequency).
2
-0.49 to 0.00 Hz
The prerequisite for a connect command being issued for the MCB is that the
differential frequency is above the configured differential frequency.
[-0.10 Hz]
This value specifies the lower frequency limit (negative value corresponds to
negative slip → busbar frequency is less than the mains frequency).
2
0.0 to 60.0°
The prerequisite for a connect command being issued for the MCB is that the
leading phase angle between busbar and mains is below the configured max‐
[7.0°]
imum permissible angle.
Notes
This parameter is only displayed, if parameter
"Phase matching".
2
-60.0 to 0.0°
The prerequisite for a connect command being issued for the MCB is that the
lagging phase angle between busbar and mains is below the configured max‐
[-7.0°]
imum permissible angle.
Notes
This parameter is only displayed, if parameter
"Phase matching".
2
0.0 to 60.0 s
This is the minimum time that the generator/busbar voltage, frequency, and
phase angle must be within the configured limits before the breaker will be
[3.0 s]
closed.
Notes
This parameter is only displayed, if parameter
"Phase matching".
2
[On]
A dead busbar closure is allowed if the required conditions are met.
Off
An MCB close command to a dead busbar is prevented. Synchronization is
still possible.
2
Determined by
Once the conditions of the LogicsManager have been fulfilled the MCB will be
LogicsManager
enabled.
[(09.06 & !
08.07) & !07.05]
Notes
DI 6 is pre-assigned by default to this function, but may be configured freely.
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
easYgen-2200/2500 | Genset Control
1768 Ä p.
95).
5810 Ä p. 136
and
5811 Ä p.
5730 Ä p. 205
5730 Ä p. 205
5730 Ä p. 205
1766 Ä p.
95) and
136), the "Command:
is configured to
is configured to
is configured to