Example
Fig. 193: LogicsManager function
37535B
To operate the easYgen in this configuration correctly, the fol‐
lowing needs to be done:
The easYgen requires an external feedback, that the drive
n
system will be started. That is the precondition for the easYgen
to trigger the delayed monitoring function, which activates, after
a delay time, the speed related monitoring functions. (under‐
speed, underfrequency, undervoltage, etc.)
The easYgen requires an external feedback, that the drive
n
system will be stopped. That is the precondition for the
easYgen to deactivate the speed related monitoring functions.
This avoids upcoming alarms due the drive system is stopped.
The easYgen must be directed to switch into the active opera‐
n
tional mode or to exit this operational mode. The operational
mode proceeds with the actions according to the configured
application and transition modes.
The following section shows a practical example, to explain in
detail the described above configuration.
Fig. 193 shows the LogicsManager "Firing speed" (parameter
12500 Ä p.
lows:
The external start/stop device gives an feedback to the
n
easYgen via discrete input [DI 02] ("09.02 Discrete input 2")
that the drive system will be started or already is started.
"Firing speed"
When simultaneously the firing speed ("02.01 Firing speed") is
n
reached, the equation becomes TRUE and the delayed moni‐
toring function will be triggered.
For security reasons a closed GCB ("04.06 GCB closed")
n
forces the monitoring too.
easYgen-2200/2500 | Genset Control
Special Applications > Start/Stop Logic Mode "Off"
The LogicsManager "Firing speed" (parameter
12500 Ä p.
239) has a special function, if the "Start/
stop logic mode" (parameter
ured to "Off". When the LogicsManager becomes
TRUE, the delayed monitoring function alarms are trig‐
gered, which are delayed by the engine speed. If they
become FALSE all engine speed related monitoring
functions are switched off. The LogicsManager "Start
req. in AUTO" (parameter
cial function if the "Start/stop logic mode" (parameter
3321 Ä p.
229) is configured to "Off". When the Logi‐
csManager becomes TRUE the operational mode
begins. With becoming FALSE the operational mode
will be left.
239). The LogicsManager must be configured as fol‐
Application
3321 Ä p.
229) is config‐
12120 Ä p.
246) gets a spe‐