Installation
Setup Connections > Voltage Measuring > Mains Voltage
3.2.5.2

Mains Voltage

General notes
Schematic and terminals
50
For different voltage systems, different wiring terminals
have to be used.
The easYgen-2000 Series can only measure either
the mains voltage (described in this chapter) or the
busbar voltage (Ä Chapter 3.2.5.3 "Busbar Voltage"
on page 56). The device is not able to measure both
voltages at the same time.
If parameter
rated volt.") is configured with a value between 50 and
130 V, the 120 V input terminals must be used for
proper measurement.
If parameter
rated volt.") is configured with a value between 131
and 480 V, the 480 V input terminals must be used for
proper measurement.
If the easYgen is intended to be operated in parallel
with the mains, the mains voltage measuring inputs
must be connected.
Fig. 31: Voltage measuring - mains - wiring
Terminal
Description
A
22
Mains (Busbar) voltage -
L1
B
23
C
24
Mains (Busbar) voltage -
L2
easYgen-2200/2500 | Genset Control
1803 Ä p. 100
("Mains PT secondary
1803 Ä p. 100
("Mains PT secondary
120 Vac
480 Vac
120 Vac
A
max
2.5 mm²
2.5 mm²
2.5 mm²