Configuration
Function Of Inputs And Outpu... > Discrete Outputs
4.3.2
Discrete Outputs
104
Programmable
n
–
The discrete output has been assigned a default function
using the LogicsManager.
–
The following text describes how these functions are
assigned using the LogicsManager.
–
It is possible to change the function of the discrete output if
required.
–
The following description of the outputs, labeled with "pro‐
grammable", refers to the preconfiguration.
Fixed
n
–
The discrete output has a specific function that cannot be
changed depending upon the configured application mode.
–
The discrete output cannot be viewed or changed in the
LogicsManager.
–
However, the discrete output may be programmable in
some application modes.
The discrete outputs can be "programmable" or "fixed"
depending on the application mode (param‐
eter
3401 Ä p.
For information on the function of the discrete outputs
depending on the configured application mode refer to
Ä Chapter 4.5.5 "Discrete Outputs (LogicsManager)"
on page 220.
CAUTION!
Uncontrolled operation due to faulty configuration
The discrete output "Ready for operation OFF" must
be wired in series with an emergency stop function.
This means that it must be ensured that the generator
circuit breaker is opened and the engine is stopped if
this discrete output is de-energized.
If the availability of the plant is important, this fault
must be signaled independently from the unit.