Woodward easYgen-2000 Series User Manual page 255

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
5759
Minimum run‐
ning time
4.5.11.1.4
Isolated Parallel Operation (IOP)
General notes
37535B
Configure Application > Automatic Run > Load Dependent Start Stop ...
CL
Setting range
Description
[Default]
Example 1
n
n
n
n
n
n
In this instance the assigned generator number is used to determine which
generator is brought online. Generator 1 will be started.
Example 2
n
n
n
n
n
n
n
n
n
n
n
In this instance the largest time group will determine which generator is
brought online. Generator 2 will be started because it is in time group 5.
Notes
This parameter is only effective if fit service hours (parameter
is configured to "Equal".
2
0 to 32000 s
If a genset has been started by the LDSS function, it continues to operate at
least for this time even if it would have been stopped before.
[180 s]
This timer is started with the closure of the GCB. If an emergency run is
active (
return, this timer will be overridden and the load is transferred back to the
mains after the mains settling time (parameter
In case of an isolated parallel operation (MCB open), the first
genset will be connected to the de-energized busbar.
easYgen-2200/2500 | Genset Control
"Changes of engines" is configured to "All 64h"
Generator 1 has 262 maintenance hours remaining
Generator 2 has 298 maintenance hours remaining
The time group for generator 1 is calculated as: 262h/64h = 4.09 = Time
group 4
The time group for generator 2 is calculated as: 298h/64h = 4.66 = Time
group 4
Both generators are in time group 4.
Time group 4 consists of any generator that the time group calculation
total ranges from 4.00 through 4.99.
"Changes of engines" is configured to "All 64h"
Generator 1 has 262 maintenance hours remaining
Generator 2 has 345 maintenance hours remaining
Generator 3 has 298 maintenance hours remaining
The time group for generator 1 is calculated as: 262h/64h = 4.09 = Time
group 4
The time group for generator 2 is calculated as: 345h/64h = 5.39 = Time
group 5
The time group for generator 3 is calculated as: 298h/64h = 4.66 = Time
group 4
Generators 1 and 3 are in time group 4.
Time group 4 consists of any generator that the time group calculation
total ranges from 4.00 through 4.99.
Generator 2 is in time group 5.
Time group 5 consists of any generator that the time group calculation
total ranges from 5.00 through 5.99.
Ä Chapter 4.5.10 "Emergency Run" on page 244 ) and the mains
Configuration
5755 Ä p.
253)
2801 Ä p.
135) has expired.
255