Application mode
Symbol
None
GCBopen
GCB
GCB/MCB
37535B
For detailed information on the application modes and
special applications refer to Ä Chapter 6.2 "Basic
Applications" on page 360.
Function
No breaker control.
This application mode provides the following functions:
n
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power,
coolant temperature, oil pressure, etc.)
n
Engine start/stop
GCB control (open)
This application mode provides the following functions:
n
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power,
coolant temperature, oil pressure, etc.)
n
Engine start/stop
n
Engine/generator protection (relay output to open GCB)
n
Mains failure detection with mains decoupling (GCB)
GCB control (open/close)
This application mode provides the following functions:
n
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power,
coolant temperature, oil pressure, etc.)
n
Engine start/stop
n
Engine/generator protection (relay output to open GCB)
n
GCB operation (relay output to close GCB)
n
Mains failure detection with mains decoupling (GCB)
GCB/MCB control (open/close)
This application mode provides the following functions:
n
Measuring of engine/generator parameters (i.e. voltage, frequency, current, power,
coolant temperature, oil pressure, etc.)
n
Engine start/stop
n
Engine/generator protection (relay output to open GCB)
n
GCB operation (relay output to close GCB)
n
MCB operation (relay outputs to open and close MCB)
n
Mains failure detection with mains decoupling (GCB and/or MCB)
n
Auto mains failure operation (AMF)