Woodward easYgen-2000 Series User Manual page 52

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Installation
Setup Connections > Voltage Measuring > Mains Voltage
3.2.5.2.2
Parameter Setting '3Ph 3W' (3-phase, 3-wire)
Mains windings
Measuring inputs
Terminal assignment
3Ph 3W
Wiring terminals
Rated voltage (range)
120 V (50 to 130 V
Measuring range (max.)
0 to 150 Vac
Terminal
A
22
Phase
L1
52
For different voltage systems, different wiring terminals
have to be used.
Incorrect measurements are possible if both voltage
systems use the same N terminal.
Table 13: Mains windings - 3Ph 3W
Fig. 33: Measuring inputs - 3Ph 3W
)
eff.
C
E
G
24
26
28
L2
L3
---
For different voltage systems, different wiring terminals
have to be used.
easYgen-2200/2500 | Genset Control
480 V (131 to 480 V
)
eff.
0 to 600 Vac
B
D
F
23
25
27
L1
L2
L3
H
29
---
37535B

Advertisement

Table of Contents
loading

Table of Contents