3.2.5.2.3
Parameter Setting '1Ph 3W' (1-phase, 3-wire)
Mains windings
Table 14: Mains windings - 1Ph 3W
Measuring inputs
Terminal assignment
1Ph 3W
Wiring terminals
Rated voltage (range)
120 V (50 to 130 V
Measuring range (max.)
0 to 150 Vac
Terminal
A
22
Phase
L1
37535B
Setup Connections > Voltage Measuring > Mains Voltage
Fig. 34: Measuring inputs - 1Ph 3W
)
eff.
C
E
G
24
26
28
N
L3
N
For different voltage systems, different wiring terminals
have to be used.
Incorrect measurements are possible, if both voltage
systems use the same N terminal.
easYgen-2200/2500 | Genset Control
480 V (131 to 480 V
)
eff.
0 to 600 Vac
B
D
F
23
25
27
L1
N
L3
Installation
H
29
N
53