Woodward easYgen-2000 Series User Manual page 260

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Application > Automatic Run > Load Dependent Start Stop ...
ID
Parameter
5769
MOP Hyste‐
resis
5768
MOP Reserve
power
5770
MOP Max. gen‐
erator load
5771
MOP Min. gen‐
erator load
260
CL
Setting range
Description
[Default]
2
0 to 65000 kW
Start stop mode configured to "Reserve power":
[20 kW]
If the reserve power is sufficient to stop one genset without falling below the
reserve power threshold and the hysteresis configured here, a genset will be
stopped.
If the generator load falls below the minimum load threshold minus the hyste‐
resis configured here, the last genset will be stopped.
Notes
The importance of this parameter depends on the setting of the start stop
mode (parameter
2
0 to 999999 kW
The minimum reserve power in mains parallel operation is configured here.
[50 kW]
This is the maximum expected load swing on the busbar, which shall be sup‐
ported by the gensets.
If the reserve power falls below this value, the load-dependent start/stop func‐
tion will start another genset.
Notes
This parameter is only effective if start stop mode (parameter
is configured to "Reserve power".
This parameter is not visible and therefore not configurable in the
easYgen-2000 Series. Please refer to
eter Alignment" on page 187 for details.
2
0 to 100 %
If the generator load exceeds the threshold configured here, the load-
dependent start/stop function will start another genset.
[70 %]
Notes
This parameter is only effective if start stop mode (parameter
is configured to "Generator load".
The maximum generator load must be configured higher then the minimum
generator load for proper operation.
This parameter is not visible and therefore not configurable in the
easYgen-2000 Series. Please refer to
eter Alignment" on page 187 for details.
2
0 to 100 %
If the generator load falls below the threshold configured here, the load-
dependent start/stop function will stop a genset.
[30 %]
If only a few gensets are operating in a multi-genset application, the MOP
Dynamic (parameter
genset.
Notes
This parameter is only effective if start stop mode (parameter
is configured to "Generator load".
The maximum generator load must be configured higher then the minimum
generator load for proper operation.
This parameter is not visible and therefore not configurable in the
easYgen-2000 Series. Please refer to
eter Alignment" on page 187 for details.
easYgen-2200/2500 | Genset Control
5752 Ä p.
252).
Ä Chapter 4.4.6.10 "Multi-Unit Param‐
Ä Chapter 4.4.6.10 "Multi-Unit Param‐
5758 Ä p.
261) will also be considered when stopping a
Ä Chapter 4.4.6.10 "Multi-Unit Param‐
5752 Ä p.
252)
5752 Ä p.
252)
5752 Ä p.
252)
37535B