Configuration
Configure Application > Inputs And Outputs > Analog Inputs
4.5.2

Inputs And Outputs

4.5.2.1

Analog Inputs

ID
Parameter
3631
Display tem‐
perature in
3630
Display pres‐
sure in
4.5.2.1.1
Characteristic Curves Setup
General notes
Fig. 85: Characteristic curves (example table)
208
CL
Setting range
Description
[Default]
1
[°C ]
The temperature is displayed in °C (Celsius).
°F
The temperature is displayed in °F (Fahrenheit).
1
[bar ]
The pressure is displayed in Bar.
psi
The pressure is displayed in psi.
The characteristic curves of "Table A" and "Table B" (freely config‐
urable over 9 defined percentage points) are independently config‐
urable for all analog inputs. Each percentage point may be scaled
to related values measured from the analog input (0 to 500 Ohm or
0 to 20 mA), so that the actual display reflects the measured
values (i.e. 200 to 600 kW).
The created characteristic curves can be set for visualization and
monitoring via the configuration to "Table A" (for Table A) as well
as "Table B" (for Table B).
The X and Y junction may be moved within the range of values (the
junctions don't have to be equidistant).
When configuring the X coordinates, ensure the coordinates
always increase in scale continuously.
easYgen-2200/2500 | Genset Control
37535B