Appendix
Data Protocols > Additional Data Identifier > Transmit Data
Bit 11 = 1 (ID 545)
Bit 10 = 1 (ID 546)
Bit 9 = 1 (ID 547)
Bit 8 = 1 (ID 548)
Bit 7 = 1 (ID 549)
Bit 6 = 1 (ID 550)
Bit 5 = 1 (ID 551)
Bit 4 = 1 (ID 552)
Bit 3 = 1 (ID 553)
Bit 2 = 1 (ID 554)
Bit 1 = 1 (ID 555)
Bit 0 = 1 (ID 556)
Remote active power setpoint
Remote power factor setpoint
530
Remote control bit 12 (command variable 04.55)
Remote control bit 11 (command variable 04.54)
Remote control bit 10 (command variable 04.53)
Remote control bit 9 (command variable 04.52)
Remote control bit 8 (command variable 04.51)
Remote control bit 7 (command variable 04.50)
Remote control bit 6 (command variable 04.49)
Remote control bit 5 (command variable 04.48)
Remote control bit 4 (command variable 04.47)
Remote control bit 3 (command variable 04.46)
Remote control bit 2 (command variable 04.45)
Remote control bit 1 (command variable 04.44)
easYgen-2200/2500 | Genset Control
Object 21FBh (Parameter 507)
This value may be used as data source "[05.06] Inter‐
face pwr. setp." via the Analog Manager. No password
is required to write this value.
This object is required to transmit the active power set‐
point for active power control.
The data type is INTEGER32.
The value is scaled in [kW * 10].
Example
100 kW = 1000 = 03E8h
–
Object 21FCh (Parameter 508)
This value may be used as data source "[05.12] Inter‐
face PF setp." via the Analog Manager. No password
is required to write this value.
This object is required to transmit the power factor set‐
point for power factor control.
The data type is INTEGER16.
The valid range for this value is [-710 to 1000 to 710].
Example
PF (cosphi) = c0.71 (capacitive) = -710 = FD3Ah
–
PF (cosphi) = 1.00 = 1000 = 03E8h PF (cosphi) =
i0.71 (inductive) = 710 = 02C6h Remote Fre‐
quency Setpoint - Object 21FDh
37535B