Woodward easYgen-2000 Series User Manual page 225

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
5202
PWM signal
5216
5210
PWM output
level
5224
Setting ranges
37535B
CL
Setting range
Description
[Default]
Example
f the value configured here is 75 %, the maximum output range of +/-20 mA /
+/-10 V has a upper limit of 10 mA / 5 V.
2
On
A PWM signal will be output on the respective analog output.
[Off]
An analog signal will be output on the respective analog output.
Notes
The amplitude of the PWM signal to be utilized is configured in "PWM output
level" (parameter
The PWM signal will also be limited by parameter
5201 Ä p. 224/5215 Ä p. 224
and
is user defined.
2
0.00 to 10.00 V
If PWM has been enabled in parameter
level of the PWM signal may be adjusted here.
[10.00 V]
Type
Current
Voltage
easYgen-2200/2500 | Genset Control
Configure Application > Analog Outputs 1/2
5210 Ä p.
225).
or parameters
5209 Ä p. 224/5223 Ä p. 224
Setting in parameter
Jumper
5201/5215
neces‐
sary
+/-20mA (+/-10V)
no
+/-10mA (+/-5V)
0 to 10mA (0 to 5V)
0 to 20mA (0 to 10V)
4 to 20mA
10 to 0mA (5 to 0V)
20 to 0mA (10 to 0V)
20 to 4mA
User defined
+/-20mA (+/-10V)
yes
+/-10mA (+/-5V)
+/-3V
+/-2.5V
+/-1V
0 to 10mA (0 to 5V)
0.5V to 4.5V
0 to 20mA (0 to 10V)
10 to 0mA (5 to 0V)
4.5V to 0.5V
Configuration
5208 Ä p. 224/5222 Ä p. 224
if parameter
5201 Ä p. 224/5215 Ä p. 224
5203 Ä p. 224/5217 Ä p. 224
Range
Lower
level
+/-20mA
-20 mA
+/-10mA
-10 mA
0-10mA
0 mA
0-20mA
0 mA
4-20mA
4 mA
10-0mA
10 mA
20-0mA
20 mA
20-4mA
20 mA
+/-10V
-10 Vdc
+/-5V
-5 Vdc
+/-3V
-3 Vdc
+/-2.5V
-2.5Vdc
+/-1V
-1 Vdc
0 to 5V
0 Vdc
0.5 to
0.5 Vdc
4,5V
0 to 10V
0 Vdc
5 to 0V
5 Vdc
4.5 to
4.5 Vdc
0,5V
the
Upper
level
+20 mA
+20 mA
10 mA
20 mA
20 mA
0 mA
0 mA
4 mA
+10 Vdc
+5 Vdc
+3 Vdc
+2.5 Vdc
+1 Vdc
5 Vdc
4.5 Vdc
10 Vdc
0 Vdc
0.5 Vdc
225