5.2.4.3

Sequencing

Fig. 124: Sequencing screen
37535B
Front Panel Access > Specialised Menu Screens > Sequencing
Symbol/Softkey
Description
Indicates that corresponding alarm condition is still present.
Acknowledge the selected alarm message (displayed
inverted).
Acknowledgement is only possible, if the alarm condi‐
tion is no longer present. If the Alarm LED is still
flashing (an alarm is present, which has not yet been
acknowledged as 'Seen'), this softkey resets the horn
and acknowledges the alarm as 'Seen'.
The sequencing screen shows all gensets participating in load
sharing. The operation mode of each genset as well as the state of
its GCB is shown on this screen.
Symbol
Description
AUTOMATIC Mode is active
MANUAL Mode is active
STOP Mode is active
GCB of respective genset in sequence is closed.
GCB of respective genset in sequence is open.
The bottom field displays the actual load dependent
start/stop values. If this device is not participating in
load dependent start/stop , "LD start stop Off" is dis‐
played here.
easYgen-2200/2500 | Genset Control
Operation
349