Woodward easYgen-2000 Series User Manual page 252

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Application > Automatic Run > Load Dependent Start Stop ...
ID
Parameter
12930
LD start stop
(Load-
dependent start
stop)
5752
Start stop
mode
5753
Dead busbar
start mode
5751
Base priority
12926
LDSS Priority 2 2
252
The mains interchange load control (import/export power) has
n
been enabled or the gensets are in isolated operation
The conditions of the LogicsManager function "Load-
n
dependent start/stop" have been fulfilled
CL
Setting range
Description
[Default]
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, the load-
LogicsManager
dependent start/stop function is enabled.
[(0 & !04.27) & !
00.19]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
[Reserve
Load-dependent start stop is performed in a way that a configured minimum
power]
reserve power is maintained in the system. The reserve power is the total
generator rated power minus the total actual generator power.
If the reserve power falls below the threshold, another genset will be started.
If the reserve power is sufficient to stop one genset without falling below the
threshold, a genset will be stopped.
Generator load
Load-dependent start stop is performed in a way that a configured maximum
generator capacity utilization is not exceeded.
If the generator capacity utilization exceeds this threshold, another genset will
be started. If the generator capacity utilization is low enough to stop one
genset without exceeding the threshold again, a genset will be stopped.
2
[All]
All available gensets will be started in case of a dead busbar and remain con‐
nected to the busbar for the minimum running time (param‐
eter
figured LDSS procedure. The start delay is configured in
parameter
LDSS
The start of the gensets will be performed according to the configured LDSS
priority in case of a dead busbar.
Notes
This function cannot be used as an emergency power function in mains par‐
allel operations because it cannot control the MCB operation.
If the MCB should be operated, the emergency run function (parameter
2802 Ä p.
2
1 to 32
The priority of the genset in the load-dependent start/stop network is config‐
ured with this parameter (
[5]
on page 251 ). The lower the number configured here, the higher the priority.
This priority may be overridden by the LDSS Priority parameters (parameters
12924 Ä p.
Determined by
Once the conditions of the LogicsManager have been fulfilled, the load-
LogicsManager
dependent start/stop priority will be set to 2 (the highest priority is valid).
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
easYgen-2200/2500 | Genset Control
5759 Ä p.
255). Then the gensets will be stopped according to the con‐
2800 Ä p. 245
(Mains fail delay time).
245) must be enabled.
Ä Chapter 4.5.11.1.3 "Generator Selection"
253,
12925 Ä p.
253, and
12926 Ä p.
252).
37535B