Set the Node-ID
Fig. 187: Set the Node-ID
Fig. 189: Confirm changes
37535B
Special Applications > Setup Phoenix Expansion Mo...
1.
Using ToolKit, set the Node-ID for the configuration you are
using.
Fig. 188: Address DIP switches
2.
Setup the corresponding DIP switches accordingly.
The node address is set using DIP switches 1 through 7. DIP
switch 1 is the least significant digit of the node address and
DIP switch 7 is the most. Valid node address settings range
from 1 to 127.
Note that the UL power will need to be cycled in
order to implement any changes to the node
address. Node address 0 is reserved, and used
to auto-configure the I/O attached to the module.
The unit will not go online at address 0.
3.
Initialize the startup routine in the Phoenix device.
4.
Set parameter
to "Yes" to confirm your changes in the easYgen.
easYgen-2200/2500 | Genset Control
15134 Ä p. 317
"Configure external devices"
Application
399