Configuration
Configure Application > Analog Outputs 1/2
ID
Parameter
5203
Filter time con‐
stant
5217
5201
Selected hard‐
ware type
5215
5208
User defined
min. output
5222
value
(User defined
minimum output
value)
5209
User defined
max. output
5223
value
(User defined
maximum
output value)
224
CL
Setting range
Description
[Default]
2
A filter time constant may be used to reduce the fluctuation of an analog
output value. This filter time constant assesses the average of the signal
according to the following formula:
n
[Off]
The analog output is displayed without filtering.
1
Cut-off-frequency = 7.96 Hz (filter time constant = 0.02 s)
2
Cut-off-frequency = 3.98 Hz (filter time constant = 0.04 s)
3
Cut-off-frequency = 1.99 Hz (filter time constant = 0.08 s)
4
Cut-off-frequency = 0.99 Hz (filter time constant = 0.16 s)
5
Cut-off-frequency = 0.50 Hz (filter time constant = 0.32 s)
6
Cut-off-frequency = 0.25 Hz (filter time constant = 0.64 s)
7
Cut-off-frequency = 0.13 Hz (filter time constant = 1.28 s)
Notes
The filter is not applied to the analog output display value, i.e. the end value
of the analog output is displayed immediately.
2
This parameter is used to configure the appropriate type of analog controller
signal. The range of the analog output is configured here.
Off
No analog output signal will be issued.
user defined
A maximum range of +/-20 mA / +/-10 V may be limited using the parame‐
ters
[0-20mA /
0-10V]
Notes
For a list of available signal ranges refer to
selection" Table on page 225
2
0.00 to 100.00
The minimum output value, which shall correspond with the minimum value of
%
the output range, must be entered here.
[0.00 %]
Notes
This parameter is only active, if parameter
set to "user defined".
Example
If the value configured here is 25 %, the maximum output range of +/-20 mA /
+/-10 V has a lower limit of -10 mA / -5 V.
2
0.00 to 100.00
The maximum output value, which shall correspond with the maximum value
%
of the output range, must be entered here.
[100.00 %]
Notes
This parameter is only active, if parameter
set to "user defined".
easYgen-2200/2500 | Genset Control
Cut-off-frequency =
1 / (20 ms * 2 * π * 2
N - 1
)
whereby "N" is this parameter.
5208 Ä p. 224
and
5209 Ä p. 224
to obtain a user defined range.
Ä "Analog outputs - signal type
5201 Ä p. 224/5215 Ä p. 224
5201 Ä p. 224/5215 Ä p. 224
is
is
37535B