9.5.3

Status Messages

Message text
Meaning
ID
AUTO mode ready
Automatic mode ready for start
13253
The unit is waiting for a start signal in Automatic operating mode and no alarm of class C, D, E, or F is
present.
Aux. serv. postrun
Postrun of the auxiliary operation is active
13201
After the engine has stopped, auxiliary operations are enabled. These operations ensure that required
equipment which is necessary for the operation of the engine continues to run (i.e. electric cooling fan).
Aux. services prerun
Prerun of the auxiliary operation is active
13200
Before the engine is started the signal "aux. services prerun" is enabled, so that all required equipment
which is necessary for the operation of the engine can be initialized, started or switched.
Cool down
Coasting of the engine is active
13204
The no load operation is performed prior to the stopping of the engine. The no load operation is utilized to
cool the engine.
Crank protect
Starter protection
13214
To prevent the starter from being damaged by an engine that is rotating, a crank protection delay is active
to ensure that the engine has time to stop rotating.
Critical mode
Critical mode (Sprinkler operation) is active
13202
The sprinkler operation is activated.
Emergency/Critical
Emergency operation during active critical operation
13215
Critical operation is activated.
Emergency run
Emergency power operation
13211
After the control unit detects that a mains fault has occurred, the engine is started after the emergency
delay timer expires. The MCB is opened, the GCB is closed, and the generator set assumes the load. If
the generator set is already running, operations continue until the emergency power operation conditions
no longer exist. If the mains return, the mains settling timer becomes active first (see below).
GCB dead bus close
Dead bus closing of the GCB
13209
The GCB is closed onto the de-energized busbar. The measured busbar voltage is below the configured
dead bus detection limit.
GCB → MCB Delay
GCB – MCB delay time is active
13261
If the breaker logic is configured to Open Transition and a transfer from generator to mains supply is initi‐
ated, the transfer time delay will start after the replay "GCB is open" is received. The MCB close command
will be issued after the transfer time has expired.
GCB open
The GCB is being opened
13255
A GCB open command has been issued.
Gen. stable time
Generator stable time is active
13250
If the engine monitoring delay timer has expired, the generator settling time starts. This permits for an
additional delay time before the breaker is closed in order to ensure that none of the engine delayed
watchdogs trips.
Idle run active
The control is in idle mode
13216
No undervoltage, underfrequency, and underspeed monitoring is performed in idle mode. The flexible
limits 13 through 16 are not monitored.
Ignition
Enable the ignition (Gas engine)
13213
After the purging operation and before the fuel solenois opened.
37535B
easYgen-2200/2500 | Genset Control
Event And Alarm Reference > Status Messages
Appendix
589