Woodward easYgen-2000 Series User Manual page 150

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Mains > QV Monitoring
Fig. 81: QV monitoring - schematic
ID
Parameter
3292
Monitoring
3285
Limit under‐
voltage
3287
Minimum cur‐
rent
3291
Reactive power
threshold
150
CL
Setting range
Description
[Default]
2
On
QV monitoring is carried out according to the following parameters.
[Off]
No monitoring is carried out.
2
45 to 150 %
The percentage voltage value that is to be monitored is defined here.
[85 %]
If the voltages of all phases (one phase in 1Ph 2W system) are below this
limit, the voltage condition for tripping the monitoring function is TRUE.
Notes
This value refers to the "Generator rated voltage" (parameter
2
0 to 100 %
The percentage current value that is to be monitored is defined here.
[10 %]
If the average generator current has been exceeded this limit, the current
condition for tripping the monitoring function is TRUE.
Notes
This value refers to the "Generator rated current" (parameter
2
2 to 100 %
The percentage reactive value that is to be monitored is defined here.
[5 %]
If the absolute value of reactive power Q is higher than this threshold, the
reactive power condition for tripping the monitoring function is TRUE.
Notes
This value refers to the "Gen. rated react. power [kvar]" (parameter
1758 Ä p.
easYgen-2200/2500 | Genset Control
95).
1766 Ä p.
95).
1754 Ä p.
95).
37535B