Application Mode A02 (Gcbopen) - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Engine operation in AUTOMATIC
(basic function)
6.2.2

Application Mode A02 (GCBopen)

37535B
Basic Applications > Application Mode A02 (GCBo...
If the easYgen is intended to be operated in parallel
with the mains, the mains voltage measuring inputs
must be connected.
Engine starts, if
The LogicsManager "Start req. in AUTO" is fulfilled (TRUE)
n
AND
A shut down alarm is not present AND
n
The engine is ready for operation
n
Engine stops, if
The reply GCB is open AND the LogicsManager "Start req. in
n
AUTO" is not fulfilled (FALSE) OR
A shut down alarm occurs
n
Being parallel to mains or to other generator, the generator power
will be reduced before.
Refer to Ä Chapter 4.5.11 "Automatic Run"
on page 246 for details.
This application mode (
applications.
In this case, the easYgen will function as an engine control with
generator and engine protection. The control unit can only open
the GCB. Emergency mode (AMF operation) is not supported in
this application mode.
easYgen-2200/2500 | Genset Control
) may be used for isolated operation
Application
361