Fig. 213: Active power setpoint
Fig. 214: Power factor setpoint
Fig. 215: Frequency setpoint
Fig. 216: Voltage setpoint
6.6.2

Changing Parameter Settings

6.6.2.1

Parameter Setting

37535B
Modbus Applications > Changing Parameter Settings > Parameter Setting
2.
Double-click the address to issue a Write Register com‐
mand.
ð Fig. 213 shows how bit 7 is set to enable the active
power setpoint 2.
Fig. 214 shows how bit 6 would be set to enable the
power factor setpoint 2.
Fig. 215 shows how bit 5 would be set to enable the fre‐
quency setpoint 2.
Fig. 216 shows how bit 4 would be set to enable the
voltage setpoint 2.
The example tables below are excerpts. Refer to the
following chapters for the complete parameter lists:
Ä Chapter 4.1.4 "Enter Password" on page 89
Ä Chapter 4.2 "Configure Measurement"
on page 93
Be sure to enter the password for code level 2 or
higher for the corresponding interface to get access for
changing parameter settings.
easYgen-2200/2500 | Genset Control
Application
433