Engine Unintended Stop - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
2500
Monitoring
2503
Maximum stop
delay
2501
Alarm class
2502
Self acknowl‐
edge
4.4.3.9

Engine Unintended Stop

General notes
37535B
CL
Setting range
Description
[Default]
2
[On]
Monitoring of the stop sequence is carried out according to the following
parameters.
Off
Monitoring is disabled.
2
3 to 999 s
The maximum permissible time between the output of a stop command and
the reply that the engine is stopped successfully is defined here.
[30 s]
Notes
If the engine cannot be stopped within this time (this means speed via the
Pickup, frequency via the generator voltage, or the LogicsManager is
detected) the action specified by the alarm class is initiated.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[F]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
If an engine stop has been detected without a stop command being
issued, an alarm will be initiated.
easYgen-2200/2500 | Genset Control
Configure Monitoring > Engine > Engine Unintended Stop
If this protective function is triggered, the display indi‐
cates "Eng. stop malfunct." and the logical command
variable "05.06" will be enabled.
We recommend to assign this monitoring function to a
discrete output to be able to shutdown the engine with
an external device to provide a shutdown redundancy.
Ä Chapter 9.5.1 "Alarm Classes"
If this protective function is triggered, the display indi‐
cates "Unintended stop" and the logical command vari‐
able "05.05" will be enabled.